Inspection / Emergency Lighting
Emergency Lighting Inspection
Emergency Lighting Backup
Will Your Emergency Lights Work When You Need Them?
Emergency lights provide lighting in corridors, stairwells, ramps, escalators, aisles, and exit passageways in the event of a power outage. If your emergency lights fail to operate properly during an emergency situation the building occupants may become disoriented. Routine maintenance of emergency and exit lighting is frequently overlooked until an emergency occurs. Regular maintenance is required by NFPA Standards, Ontario Fire Code Standards, and required manufacturer specifications.
"A functional test shall be conducted on every required emergency lighting system at 30-day intervals for a minimum. An annual test shall be conducted. Equipment shall be fully operational for the duration of the test. Written records of visual inspections and tests shall be kept by the owner for inspection by the authority having jurisdiction."
Our factory trained technicians will perform the required testing and maintenance on emergency lights and provide you with the written records as required by law. A full discharge of each unit must be performed annually.
Testing Procedures for Emergency Lights
Full function test Disconnect AC power supply to each emergency light Check battery and bulbs for operation Clean each emergency light and lens as required Adjust beam for proper alignment / if required Place testing label on the emergency light and record in testing log
Troubleshooting/repair may also include
Check and adjust charging system voltage Check battery output voltage Check line voltage to remote fixtures
EMERGENCY POWER SYSTEMS
EMERGENCY POWER SYSTEMS
Annually Liquid fuel tanks shall be drained and refilled with a fresh supply at least once a year.
6.7.1.5.(1)
MEANS OF EGRESS
Monthly Doors in fire separations shall be inspected monthly.
2.2.3.4.
As Needed Doors in fire separations in occupied buildings shall be checked as frequently as necessary to ensure that they remain closed.
Sentence (1) does not apply to:
(a) doors designed to close automatically in the event of a fire, or
(b) doors for which an approved fire safety plan contains provisions for closing in the event of a fire.
2.2.3.5.(1) 2.2.3.5.(2)
As Needed Access to exits, including corridors used by the public and exits, including outside areas, shall be maintained free of obstructions.
2.7.1.7.(1)
As Needed Required exit signs shall be clearly visible and maintained in a clean and legible condition.
2.7.3.1.
Monthly Pilot lights on emergency lighting unit equipment shall be checked monthly for operation.
2.7.3.3.(1)
Monthly Emergency lighting unit equipment shall be inspected monthly to ensure that:
(a) the terminal connections are clean, free of corrosion and lubricated when necessary,
(b) the terminal clamps are clean and tight as per manufacturer's specifications,
(c) the electrolyte level and specific gravity are maintained as per manufacturer's specifications, and
(d) the battery surface is kept clean and dry.
2.7.3.3.(2)
Monthly Emergency lighting unit equipment shall be tested monthly to ensure that the emergency lights will function upon failure of the primary power supply.
2.7.3.3.(3)(a)
Yearly Emergency lighting unit equipment shall be tested annually to ensure that the unit will provide emergency lighting for a duration equal to the design criteria under simulated power failure conditions.
After completion of the test required in Clause (3)(b), the charging conditions for voltage and current and the recovery period shall be tested to ensure that the charging system is in accordance with the manufacturer's specifications. 2.7.3.3.(3)(b) 2.7.3.3.(4)


